Data Center Liquid Cooling
QS-L08 70 kW In-Row Liquid-to-Air CDU
Reference size: 600 × 1200 × 2300 mm
Custom dimensions, construction and configurations are available to meet project requirements.
Technical specifications
- Configuration code
- QS-L08
- Overall / configured size
- 600 × 1200 × 2300 mm
- Heat transfer type
- Liquid-to-air, in-row installation
- Ref. cooling capacity
- 70 kW (40 °C supply liquid, 15 °C approach temperature differential)
- Ref. liquid flow rate
- 70 L/min (40 °C supply liquid)
- Ref. airflow
- 7 fans, 11100 m³/h
- Ref. power supply
- 208-240 V, single-phase
QISHUN METAL New Product Selection Guide · PDF pp. 19. Confirm options and combinations when ordering.
Dimensions, load, protection ratings and performance are reference values for the configuration shown. Confirm final specifications against the approved drawings and quotation.
What to specify
- Required dimensions and installation layout
- Project operating conditions and scope of supply
CATALOG REFERENCE
Original catalog specifications
Use the configuration code when requesting a project quotation.
Original configuration specifications PDF p. 19
Open full-size table
Explore other products

CONFIGURATION QS-L01
QS-L01 35 kW Rack-Mount Liquid-to-Liquid CDU
Reference size: 445 × 898 × 171.5 mm

CONFIGURATION QS-L02
QS-L02 300 kW In-Row Liquid-to-Liquid CDU
Reference size: 600 × 1200 × 2000 mm (W × D × H)

CONFIGURATION QS-L04
QS-L04 Outdoor Primary-Side Cooling Distribution Unit (EDU)
Reference size: 1400 × 980 × 1600 mm (L × W × H)