Data Center Liquid Cooling
QS-L02 300 kW In-Row Liquid-to-Liquid CDU
Reference size: 600 × 1200 × 2000 mm (W × D × H)
Custom dimensions, construction and configurations are available to meet project requirements.
Technical specifications
- Configuration code
- QS-L02
- Overall / configured size
- 600 × 1200 × 2000 mm (W × D × H)
- Heat transfer type
- Liquid-to-liquid, in-row floor-standing unit
- Ref. cooling capacity
- 300 kW
- Unit configuration
- Dual pumps and dual power feeds
- Ref. net weight
- 520 kg
- Secondary liquid supply
- ≥40 °C, supply-to-return differential ≥10 °C
- Primary liquid supply
- ≤35 °C, supply-to-return differential ≤10 °C
- Ref. power supply
- 3-phase 380 V AC ±10%, 50 Hz ±3 Hz, 3 kW rated
- Ref. working fluid
- Water, aqueous ethylene glycol or aqueous propylene glycol
QISHUN METAL New Product Selection Guide · PDF pp. 16. Confirm options and combinations when ordering.
Dimensions, load, protection ratings and performance are reference values for the configuration shown. Confirm final specifications against the approved drawings and quotation.
What to specify
- Required dimensions and installation layout
- Project operating conditions and scope of supply
CATALOG REFERENCE
Original catalog specifications
Use the configuration code when requesting a project quotation.
Original configuration specifications PDF p. 16
Open full-size table
Explore other products

CONFIGURATION QS-L01
QS-L01 35 kW Rack-Mount Liquid-to-Liquid CDU
Reference size: 445 × 898 × 171.5 mm

CONFIGURATION QS-L04
QS-L04 Outdoor Primary-Side Cooling Distribution Unit (EDU)
Reference size: 1400 × 980 × 1600 mm (L × W × H)

CONFIGURATION QS-L05
QS-L05 Direct-Plug Cold-Plate Liquid Cooling Cabinet
Reference size: W 600 mm, D 1200/1400 mm, H 2000/2200 mm